Circutor RGU-10 Earth Leakage Relay

0 out of 5

£71.00 excl. VAT

  • Delay: 00.2-10s on instantaneous or selective
  • Dimensions: 3-DIN Module
  • Auxillary Power supply: 230VAC (20% difference)
  • Output contacts: 250 Vac, 6A
  • Remote signal: Pre-alarm
View basket

Description

Electronic earth leakage protection relay of the WG series, connected to the external
transformers of the WG / WGC series. Superimmunized type relay with high frequency
currents filtering and high immunity. True RMS measurement (TRMS).

  • Delay: 00.2-10s on instantaneous or selective
  • Dimensions: 3-DIN Module
  • Auxillary Power supply: 230VAC (20% difference)
  • Output contacts: 250 Vac, 6A
  • Remote signal: Pre-alarm

Product information

The RGU-10 relays associated with WG transformers offer smart earth leakage protection.
Their design features guarantee maximum security and electrical service continuity,
avoiding unwanted tripping.
Viewing the instantaneous leakage value on the display, together with the prealarm
indicators, makes it possible to obtain information on the status of lines to be protected,
and to perform adequate preventive maintenance.

Additional information

Brand

Eastron

Mounting

Panel Mount

Certification

MID

Connection

Communication Type

Class A super-immunised
Measurement True root mean square (TRMS)
Sensitivity 0.03…3 A
0.03…30 A
(PROGRAMMING)
Delay Time defined: 0.02…10 s
Inverse curve: Instantaneous
or selective
Earth leakage transformer External, WG / WGC series
Test and reset With built-in buttons, T & R
Remote control External test option
Associated circuit breaker Contactor or circuit
breaker + trigger coil
LED indicators Power supply voltage
Leakage trip
Disconnection of external transformer
Prealarm
Display Trip current (red display when tripped)
Parameter programming
Instantaneous leakage current
Disconnection of external transformer
Remote signaling Prealarm
Display of parameters via RS-485
communication (RGU-10 C)
Circuit breaker control Via an NO/NC switched relay,
depending on the connection
with the circuit breaker
Electrical features Auxiliary power supply 230 Vac (± 20%) 50 / 60 Hz
(other values on demand)
Output contacts 250 Vac, 6 A
Operating temperature -10 ºC…+50 ºC
Mechanical features Attachment DIN 46277 rail (EN 50022)
Dimensions 3 modules
Weight 236 g
Protection degree IP 20 on terminals, IP 41 on back panel
Standards IEC 60947-2, IEC 60755, IEC 61008, IEC 62020

IEC 60947-2, IEC 60755, IEC 61008, IEC 62020

Vendor Information

  • Address:
  • No ratings found yet!

General Enquiries

There are no enquiries yet.