Eastron Smart X96-5 MID 96×96 Panel Meter
£111.06 excl. VAT
- MID Certified to Class C (0.5%) accuracy
- Designed and tested in the UK by an independent laboratory
- 1/5A Current transformer operated
- Individual harmonics up to 63rd level (Class 1)
- Internal three phase power supply
- Highly visible backlit display from all angles
- Programmable reverse flow for right/left side of breaker CT installation.
- Built in Modbus and Pulsed outputs
- Free Configuration software
- Description
- Additional information
- Reviews (0)
- Specification
- Certifications & Standards
- Vendor Info
- More Products
- Store Policies
- Enquiries
Description
The SMART X96 series is an advanced multifunction three-phase energy monitoring solution with optional outputs such as Pulsed, RS485 RTU Modbus and Mbus. Equipped with configuration and display buttons for ease of navigation through the various parameters and settings. Housed for 96mm panel mounting, IP51 protection and 1/5A current transformer operated. Selectable measurement modes using our free configurations software for kWh display, Total kWh (Import + Export), Import kWh and Net kWh (Export – Import) Certified in the UK according to EU Directive 2014/32/EU. MID Certificate number 0120 / SGS0288.
Displayed Parameters
- Phase to Neutral Voltage (V)
- Phase to Phase Voltage (V)
- Phase Current (A)
- Frequency (Hz)
- Active Power (kW)
- Reactive Power (kVAr)
- Apparent Power (kVA)
- Power Factor (PF)
- Total Active Energy (kWh)
- Import Reactive Energy (kVArh)
- Export Reactive Energy (kVArh)
- Power Max Demand (MD kW)
- Current Max Demand (MD A)
- Individual Harmonics Volts (63rd Level)
- Individual Harmonics Amps (63rd Level)
- Apparent Power Max Demand (MD kVA)
Product information
The Smart X96-5 is a high accuracy multifunction power meter that is a traditional wired 1/5A current transformer operated meter. Configurable for 1p2w, 3p3w and 3p4w systems and hosting a vast range of measuring parameters such as Amps, Volts, Power, Power and Current Demand (Sliding and fix scale options), Power Factor, imported and exported kWh, Individual harmonics, Phase sequence and a phase summary page. It is one of the most user-friendly multifunction power meters in the market form installation to end client use.
It is typical in most installations that the current transformers are mounted on the left-hand side of the breaker so P1 is facing the correct way. However, it is also possible to mount the current transformer on the right-hand side with P2 facing the breaker. This is possible due to the meter having the option to reverse the flow to correct this type of application.
The SMART X96-5 requires mains voltage inputs and external current transformers in order to operate, it is self-supplied via a internal three phase transformer, this means if any of the phases fail the meter will remain powered and does not require an external auxiliary supply. The Smart X96-5 meter comes complete with RS485 Modbus RTU and dual pulsed outputs as standard.
Additional information
Brand | Eastron |
---|---|
Mounting | Panel Mount |
Certification | MID |
Connection | |
Communication Type |
Be the first to review “Eastron Smart X96-5 MID 96×96 Panel Meter”
Input | |
Nominal input voltage | 100-276V AC ( L-N ) 173-480V AC( L-L) |
Max. continuous input overload voltage | 120% of nominal |
Max. short duration input voltage | 2 x nominal voltage for 1 second |
Nominal input voltage burden | <0.2VA per phase |
Nominal input current | 1/5A |
Nom. Input current burden | <0.1 VA |
Max. continuous input overload current | 120% of nominal |
Max. short duration input current | 20 x nominal current for 1 second |
Power supply | |
Operating range | Self powered (from any of the three phases) |
Supply burden | <2W / 10 VA |
Accuracy | |
Voltage (V) | 0.5% of range maximum |
Current (A) | 0.5% of range maximum |
Frequency (Hz) | 0.2% of mid-frequency |
Power factor (PF) | 1% of unity (0.01) |
Active power (W) | 1.0% of range maximum |
Reactive power (VAr) | 1.0% of range maximum |
Apparent power (VA) | 1.0% of range maximum |
Active energy (kWh) | Class 0.5S IEC62053-22 Class 1.0 IEC62053-21 |
Reactive energy (kVArh) | 1.0% of range maximum to IEC 62053-24 |
THD | 2% to 63rd harmonic |
Environment | |
Operating temperature | – 25ËšC to +55ËšC |
Storage temperature | -40ËšC to +70ËšC |
Relative humidity | 0 to 95%, non-condensing |
Shock | 30g in 3 planes |
Vibration | 10Hz to 50Hz, IEC 60068-2-6, 2g |
Dielectric Voltage | 4kV between voltage and current to earth |
Altitude | 3000m |
Warm-up | 1 minute |
Outputs | |
Pulsed output relay (configurable) | Opto-coupled, potential-free SPST-NO contact |
Contact Rating current | 2-27mA at 27V DC |
Contact Rating voltage | 5-27V DC |
Pulse Width | 60 / 100 / 200 ms |
Pulse rate of S0 1 | 0.01 / 0.1 / 1 / 10 / 100 kWh/kVArh |
Pulsed output of S0 2 (non-configurable) | 3200IMP/kWh |
Communications | Modbus RTU (RS485) |
Type | 2-wire half duplex |
Baud rate | 2400,4800, 9600, 19200, 38400 |
Address | 1 to 247 |
Enclosure | |
Enclosure Style | DIN 96 panel mount |
Dimensions | 96x96x62 mm |
Panel cut-out | 92x92mm |
Panel thickness | 1-2 mm |
Protection rating | Ip51 (Indoor) |
Material | UL 94-VO |
Weight | 340 g |
Cable size | 0.05mm-4mm stranded wire |
Terminals | Voltage: Shrouded screw-clamp. Current: Shrouded screw-clamp. |
- MID: EN50470-1 & EN50470-3 Class B & C
- EMC: EN61326-1 & EN61326-2-3
- LVD: EN61010-1 & EN61010-2-3
- IEC/EN62052-11:2003 Class 0.5s
Vendor Information
- Address:
- No ratings found yet!
- HotAdd to basketQuick View
Eastron SDM230-Modbus Meter
£36.35 excl. VATSingle Phase 100A Direct Connect Din Rail MID Modbus Meter
100A Single phase direct connected
MID Certified (B and D)
Bi-directional measurement for kW and kWh
Configurable pulsed output… - Add to basketQuick View
Eastron SDM120DB Meter
£17.37 excl. VATSingle Phase 45A Direct Connect Din Rail MID Pulsed Output Meter
45A Single phase direct connected
MID Certified (B and D)
1000MP/kWh Pulsed output
1 module DIN rail mounted
… - Add to basketQuick View
Eastron SDM120CT-Mbus Meter
£37.80 excl. VATSingle Phase CT Connect Din Rail MID Mbus Meter
Single Phase 5A current transformer operated
MID Certified (B and D)
Bi-directional measurement for kW and kWh
Mbus
Configurable pulsed… - Add to basketQuick View
Eastron SDM120CT-Modbus Meter
£36.35 excl. VATSingle Phase CT Connect Din Rail MID Modbus Meter
Single Phase 5A current transformer operated
MID Certified (B and D)
Bi-directional measurement for kW and kWh
RS485 Modbus
Configurable… - HotAdd to basketQuick View
Eastron SDM120-Modbus Meter
£36.35 excl. VATSingle Phase 45A Direct Connect Din Rail MID Modbus Meter
45A Single phase direct connected
MID Certified (B and D)
Bi-directional measurement for kW and kWh
Configurable pulsed output…
General Enquiries